This Author published in this journals
All Journal Energi & Kelistrikan
Claim Missing Document
Check
Articles

Found 1 Documents
Search
Journal : Energi

Penambahan DGR (Directional Ground Relay) Pada Recloser Untuk Menurunkan SAIDI / SAIFI DI ULP Lamongan Fadjar Kurniadi; Ahmad Deni Aji; Guruh Diyuksamana
Energi & Kelistrikan Vol 13 No 2 (2021): Energi dan Kelistrikan: Jurnal Ilmiah
Publisher : Sekolah Tinggi Teknik PLN

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.33322/energi.v13i2.1556

Abstract

The purpose of adding a DGR Relay to the Recloser is to improve the performance of the Recloser so that the network reliability value expressed by Saidi and Saifi is better. At ULP Lamongan, in general the protection on the installed Recloser is OCR and GFR relays. In systems with high resistance grounding, the performance of the recloser is not optimal, so it is necessary to add a DGR relay. The implementation of adding a DGR Relay to the Recloser at the Lamongan Customer Service Unit can reduce SAIDI by 86% and decrease SAIFI value by 58%.