Abstract

The serpentine tube heat exchanger is one of most widely used heat exchanger to release heat by natural convection. The ability of the tube heat exchangerto release the heat is represented by its efficiency. The present research analyzed the effect of space between tubes and the mass flow rate to the tube heat exchanger efficiency. Three serpentine tube spaces (4 cm, 5 cm, and 6 cm, respectively), and three mass flow rates (0.015 kg/s, 0.018 kg/s, and 0.021 kg/s, respectively) were varied experimentally. The result showed that the highest efficiency was reached with mass flow rate 0.021 kg/s and space between tubes 5 cm.

Copyrights © 2007






Journal Info

Abbrev

jem

Publisher

Subject

Energy Industrial & Manufacturing Engineering

Description

"Jurnal Energi dan Manufaktur" is a journal published by Department of Mechanical Engineering, University of Udayana, Bali since 2006. During 2006-2011 the journal's name was "Jurnal Ilmiah Teknik Mesin CAKRAM" (Scientific journal in mechanical engineering, CAKRAM). "Jurnal Energi dan Manufaktur" is ...