International Journal of Applied Power Engineering (IJAPE)
Vol 7, No 1: April 2018

Electrostatic Field Calculations for Liquid Nitrogen Gaps Assuming a Decisive Field Factor

Stefan Fink (Karlsruhe Institute of Technology (KIT) - Institute for Technical Physics)



Article Info

Publish Date
01 Apr 2018

Abstract

Volume effect on breakdown voltage is well known in high voltage engineering. The breakdown voltage behavior of liquid nitrogen depending on a high field volume had been quantitatively described for gap lengths up to 20 mm. Breakdown curves for longer gap lengths up to 96 mm derived from measurements with a facility “Fatelini 2” show oscillations and partly low withstand voltages. Electrostatic field calculation for such long gaps shows remarkable high field volume differences between a model for ideal sphere and models including fixation rods. Calculation for the used setup does not show monotonically increasing high field volume depending on gap length but a maximum around 60 mm which can explain the special breakdown behavior in a “mid range” gap length. Further high field calculations were done for not yet used setups in order to make considerations, e.g. for the influence of cryostat material or diameter.

Copyrights © 2018






Journal Info

Abbrev

IJAPE

Publisher

Subject

Electrical & Electronics Engineering

Description

International Journal of Applied Power Engineering (IJAPE) focuses on the applied works in the areas of power generation, transmission and distribution, sustainable energy, applications of power control in large power systems, etc. The main objective of IJAPE is to bring out the latest practices in ...