This paper introduces the uses of Robust Dynamic State Estimation (RDSE) with Phasor Measurement Unit (PMU), The M-Estimators Quadratic Linear (QL) and Square Root (SR) Estimators have been used. For the solution of the M-estimators problem, Iteratively Re-weighted Least Squares Estimation (IRLS) method is applied. In this work, we used the Decoupled Current Measurement (DCM) method to include the Phasor Measurement Unit in Robust Dynamic State Estimation. The proposed method has been tested on standard data 30-bus testing system as a case study.
Copyrights © 2014