Power Plant
Vol 4 No 2 (2016): JURNAL POWER PLANT

Pengaruh Penambahan Liquid Suction Heat Exchanger Terhadap Performa Mesin Pendingin Menggunakan R404A

Roswati Nurhasanah (Jurusan Teknik Mesin, Sekolah Tinggi Teknik – PLN)
Prayudi Prayudi (Jurusan Teknik Mesin, Sekolah Tinggi Teknik – PLN)



Article Info

Publish Date
16 Dec 2019

Abstract

One method to improve the performance of vapor compression refrigeration system using subcooling. The liquid line suction heat exchanger (LLHX) sub-cooler is a method to increase the cooling capacity of the evaporator by lowering temperature at the condenser outlet. LLHX always Increased effect of refrigeration, work of compressor and heat rejected in the condenser. The results Showed that LLHX lowering condenser exit temperature and exit temperature compressor increases as a result of superheat. LLHX exit temperature compressor with stable at 28oC compared to 16oC on the operation without LLHX in 60 minutes. The experimental results also showed that the evaporation temperature decreases of 15.2 with the addition LLHX be 17.4oC. and the latter can increase the value of COP of 2.85 until 3.5.

Copyrights © 2016






Journal Info

Abbrev

powerplant

Publisher

Subject

Automotive Engineering Energy Industrial & Manufacturing Engineering Materials Science & Nanotechnology Mechanical Engineering

Description

The Scientific Journal of "Power Plant" is a collection of scientific works by lecturers, researchers, and practitioners in the field of Mechanical Engineering that have been published since September 2012. This journal is the result of scientific work, research in the fields of Energy, Materials ...