Mitigation of high voltage induction effect on ICCP system of gas pipelines: a field case study

Rohana Ismail (Universitas Muhammadiyah Sumatera Utara)
Arnawan Hasibuan (Malikussaleh University)
Muzamir Isa (School of Electrical System Engineering, University Malaysia Perlis)
Faizar Abdurrahman (STKIP Bina Bangsa Getsempena)
Nurul Islami (STKIP Bina Bangsa Getsempena)



Article Info

Publish Date
01 Dec 2019

Abstract

An analysis of the high voltage induction effect on the impressed current cathodic protection (ICCP) system on pipelines parallel toward high voltage power lines was employed in this research. Mitigation of high voltage effect throught human and environment is necessary to implemented. Direct current induction was used to increase the electrical potential of the gas pipeline, from Klumpang to sicanang area, Indonesia. During the mitigation process, the highest induction value was obtained 0.00574 KV which is previously was 0.01732 KV, and occurred at the limit of the allowable secure touch tension value of 0.015 KV. The data that acquire from the measurement of test point of ICCP underneath the transmission line revealed a comparison data between field measurements occurred of mitigation process. The direct current induction method is found to be safe for ICCP system and environment.

Copyrights © 2019






Journal Info

Abbrev

TELKOMNIKA

Publisher

Subject

Computer Science & IT

Description

Submitted papers are evaluated by anonymous referees by single blind peer review for contribution, originality, relevance, and presentation. The Editor shall inform you of the results of the review as soon as possible, hopefully in 10 weeks. Please notice that because of the great number of ...