Pengaruh Perubahan Dimensi Filter-Drier Dan Pipa Kapiler Terhadap Coefficient Of Performance (COP) Mesin Pendingin Kulkas 2 Pintu

Khairul Mustofa (Program Studi Pendidikan Teknik Elektro Universitas Negeri Semarang)
Yohanes Primadiyono (Program Studi Pendidikan Teknik Elektro Universitas Negeri Semarang)



Article Info

Publish Date
22 Jul 2021

Abstract

COP on a cooling machine is used to reveal the performance of a cooling engine. To increase the COP value in the system, it can be done by changing the dimensions of the filter-drier and capillary pipes used. Therefore, this study was conducted to determine the effect of changing the dimensions of the filter-drier and capillary pipe on the COP and the consumption of electrical power produced by the 2-door refrigerator unit. The method used was an experimental method, namely by varying the filter drier and capillary tube dimensions of the 2-door refrigerator. Variations of filter driers used were filter driers with sizes 7 cm and 9 cm. While the capillary pipes used were 0.31 inches in diameter and 0.51 inches in diameter with a length of 200 cm and 250 cm respectively. The results obtained from this study indicate that the greatest COP value is obtained when using a 7 cm filter-drier and a capillary pipe with a diameter of 0.31 inches with a length of 200 cm, which is 2.80. The COP value also continues to decline as the size of the filter-drier and capillary pipes used increases.

Copyrights © 2021