Due increases develop the electric power system, the more effective security system is needed.One of the security systems is the earthing system at Hotel X Jimbaran. After takes measurement theaverage measurement results of 1.14 ? ~ 2.47 ? at four different location points that cause the flow ofovercurrent or overvoltage to electrical equipment. This study purpose to improve the existing earthingsystem to achieve earthing resistance <1? according to IEEE standards.This research method consist ofseveral stages, first, survey location to measure the amount of soil resistance (R) to calculate the value ofsoil resistivity (?) then calculate the value of earthing resistance according to the type of earthing systemto achieve an earthing resistance <1 ?, including the Vertical One Earthing Electrode System at Depth Z,Horizontal Earthing One Electrode System, Two Earthing Electrode System with S>L conditions, TwoEarthing Electrode Earthing System with S