International Journal of Applied Sciences and Smart Technologies
Volume 04, Issue 02, December 2022

The Effect of the Number of Cooling Pads on the Output Air Condition and Effectiveness of Air Cooler

Wibowo Kusbandono (Sanata Dharma University Yogyakarta)



Article Info

Publish Date
21 Dec 2022

Abstract

To get comfortable air, it can be done by using an air conditioner or air cooler. The electrical power used for the air cooler is relatively lower. This research aims to see the effect of the number of cooling pads on the output air condition and on the effectiveness of the air cooler. The research was conducted experimentally. The research was conducted by varying the number of cooling pads used,thick. The distance between the cooling pads is 1.5 cm. The air temperature inlet of the air cooler has a dry bulb air temperature of 30oC with an air humidity (RH) of 60%. The lowest dry bulb air temperature achieved was 24.04 oC when the number of cooling pads was 6 pieces. The highest air cooler effectiveness achieved was 0.99. Research has given satisfactory results. However, research can be developed by varying the cooling pad material or cooling pad pattern in order to obtain a small number of cooling padsKeywords: Air cooler, Effectiveness, Cooling pad

Copyrights © 2022






Journal Info

Abbrev

IJASST

Publisher

Subject

Computer Science & IT Energy Engineering Industrial & Manufacturing Engineering

Description

International Journal of Applied Sciences and Smart Technologies (IJASST) is published by Faculty of Science and Technology, Sanata Dharma University Yogyakarta-Central Java-Indonesia. IJASST is an open-access peer reviewed journal that mediates the dissemination of academicians, researchers, and ...