International Journal of Electrical and Computer Engineering
Vol 14, No 5: October 2024

Simulation of losses in a three-phase bank of transformers in the presence of harmonic distortion

Grau-Merconchin, Frank (Unknown)
Hernández Areu, Orestes (Unknown)
Nuñez Alvarez, José Ricardo (Unknown)
Montenegro-Romero, Michael (Unknown)
Quintero-Ospino, Oscar (Unknown)



Article Info

Publish Date
01 Oct 2024

Abstract

The load losses of the transformers increase considerably with the presence of harmonic distortion in the currents. Its increase can be determined using an analytical method based on ANSI/IEEE Standard C57.110. On the other hand, when it comes to three-phase banks with transformers of different capacities, delta connections, or incomplete connections, the analytical method does not allow the losses to be accurately estimated, which is why digital simulation is necessary. This work presents an adjusted model to determine the load losses in a three-phase bank of three single-phase transformers with different connection schemes. The model allows for determining load and electrical losses and calculating total additional losses. It is also possible to decide on the load capacity of the bank's transformers, the power factor, and the efficiency with which they operate under these conditions.

Copyrights © 2024






Journal Info

Abbrev

IJECE

Publisher

Subject

Computer Science & IT Electrical & Electronics Engineering

Description

International Journal of Electrical and Computer Engineering (IJECE, ISSN: 2088-8708, a SCOPUS indexed Journal, SNIP: 1.001; SJR: 0.296; CiteScore: 0.99; SJR & CiteScore Q2 on both of the Electrical & Electronics Engineering, and Computer Science) is the official publication of the Institute of ...