EPIC : Journal of Electrical Power, Instrumentation and Control
Vol 7 No 1 (2024): EPIC

Analisis Thermal Instalasi Capacitor Bank 575 kVar Menggunakan Metode Infrared Thermography

Setiawan, Agus (Unknown)
Suminto, Suminto (Unknown)
Solihin, Lili (Unknown)



Article Info

Publish Date
17 Jun 2024

Abstract

The failure of electrical components in the industry can cause production process disruptions, and even accidents. Infrared thermography is an effective method for predictive maintenance, aiming to identify potential component damage before failure occurs. This research aims to analyze the condition of a 575 kVAr capacitor bank installation using infrared thermography. The standard used is the Standard for Infrared Inspection of Electrical Systems and Rotating Equipment. The results of the study indicate that the majority of the 575 kVAr capacitor bank installation conditions fall under priority scale 3, with a maximum temperature of 44.5°C and a delta T of 18.3, which means corrective actions need to be taken with scheduling permission. Corrective actions that can be taken include inspecting cable installations, tightening cable lugs, and tightening terminal connections on contactors and MCCBs. One part that has a priority scale 4 is the MCCB and contactor of the capacitor bank on the lower front section, with a hot point value of 35.1°C and a delta T of 8.9.

Copyrights © 2024






Journal Info

Abbrev

jit

Publisher

Subject

Electrical & Electronics Engineering

Description