Analysis of Transformer Turn Ratio Test Results on 60 MVA Power Transformer at Simpang Tiga Substation PT. PLN (Persero) ULTG Prabumulih

Fajri, Satria (Unknown)
Wibowo, Pristisal (Unknown)
Hamdani, Hamdani (Unknown)



Article Info

Publish Date
31 Jan 2025

Abstract

This research aims to compare the transformer turn ratio values obtained from testing with those calculated based on the transformer's nameplate data. The testing method used was the Transformer Turn Ratio (TTR) test, conducted with the Omicron CPC100 testing device. This test measures the ratio between the number of turns in the high-voltage and low-voltage windings at each tap of the transformer. The results of the comparison between the calculated values and the test results showed a variation in the range of 0.0045 to 0.0155. The deviation values from the test were found to be within acceptable limits, with the average deviation remaining below 0.5%. The deviation values ranged from -0.07% to -0.25%, all of which are well within the allowable limits according to the SK-DIR 0520 standard. Based on these findings, the 60 MVA three-phase transformer under study is deemed to be in good condition and suitable for energizing.

Copyrights © 2025






Journal Info

Abbrev

fidelity

Publisher

Subject

Computer Science & IT Control & Systems Engineering Electrical & Electronics Engineering

Description

Focus Fidelity : Jurnal Teknik Elektro merupakan media publikasi penelitian di bidang Teknik Elektro khususnya dalam ruang lingkup Instrumentasi, kendali, pengolahan sinyal, telekomunikasi, komputer dan listrik tenaga. Naskah atau makalah yang diterbitkan telah melalui kajian dari para mitra bestari ...