Rekayasa Mekanika: Jurnal Ilmiah Teknik Mesin
Vol. 4 No. 1 (2020): April 2020

EFEKTIVITAS COOLING TOWER FAN 6P - 4051 – GB. DI PT. PUPUK SRIWIDJAJA SEKTOR STG – BB, PALEMBANG, SUMATERA SELATAN

Triyansah, Olga (Unknown)
Witanto, Yovan (Unknown)



Article Info

Publish Date
27 Oct 2020

Abstract

PT. Pupuk Sriwidjaja uses several cooling systems, one of which is the Cooling Tower Fan 6p - 4051 - GB cooling system. The cooling system is used for production machines especially in turbines. This practical work report will discuss the effectiveness of Cooling Tower Fan 6p - 4051-GB, by processing data on the temperature of incoming water, outlet water temperature, wet blub temperature and flow rate of water, then the calculation of actual data is then compared with ideal conditions, thus will be known how the performance of the Cooling Tower Fan 6p - 4051 - GB. From the analysis the ideal effectiveness value is 66.66% while for the actual effectiveness value is 64.5301%, the effectiveness decreases 2.136%. This is due to heat transfer from the system to the environment or vice versa. From the results of the analysis it can be seen in the data that the water temperature comes out at 10:00 always increases compared to the other hours. This is because at 10.00 the sunlight directly leads to the cooling tower water reservoir and on rainy days the effectiveness of the cooling tower will increase

Copyrights © 2020






Journal Info

Abbrev

rekayasamekanika

Publisher

Subject

Control & Systems Engineering Energy Industrial & Manufacturing Engineering Materials Science & Nanotechnology Mechanical Engineering

Description

Rekayasa Mekanika is scientific journal on mechanical sciences and engineering field, either pure or inter disciplinary works. This journal is a continuation of Rekayasa Mekanik which changed its name since April 2022. This journal publishes 6 articles for each issue, April and October. Starting ...