The reliability of electric power distribution systems is highly dependent on the ability of protection systems to detect and isolate faults quickly and selectively. This study aims to design and evaluate a two-level protection coordination system using a microcontroller-based Overcurrent Relay (OCR) and Ground Fault Relay (GFR) on the Achmad Jaiz Feeder at Undaan Substation. The research methodology includes system planning, literature review, hardware and software design, ETAP-based simulation, and hardware integration testing. The developed system consists of an STM32F103C8T6 microcontroller, ACS712 current sensors, relays, contactors, LCDs, keypads, and an SD card-based data logger. ETAP simulation results demonstrate a Standard Inverse relay characteristic with staged time-delay settings of 0.1 s, 0.3 s, 0.5 s, and 0.7 s to ensure protection selectivity. Hardware testing shows that the system is capable of detecting overcurrent and short-circuit faults and performing automatic tripping. During short-circuit testing, the system responded rapidly with a trip time of approximately 0.01 s. Meanwhile, overcurrent testing revealed a trip-time error exceeding 30% compared to simulation results due to sensor limitations and program implementation constraints. Overall, the proposed protection system successfully achieved its intended objectives and demonstrated its potential to enhance the reliability of power distribution network protection.
Copyrights © 2026