PLN (Persero) Ltd. Rungkut Customer Service Unit - The high load density and the length of the mangrove feeders, which are quite long, have caused several buses toward the end of the network to experience a voltage drop of 0.9421208 p.u. Therefore, it is necessary to reconfigure the network to overcome and improve the existing voltage conditions as well as optimize the loading on the feeders so that they can be evenly distributed. A comparative evaluation of the calculation of the ant chromosomes used is needed to ensure the disconnection point in reconfiguring the network. An ant colony optimization analysis on this mangrove feeder was simulated using ETAP software. The results of this drop voltage improvement analysis could be used to reconfigure the low-voltage network of mangrove feeders to 0.9933478 p.u. Consequently, it could be precise, reliable, and good at PLN Ltd. ULP Rungkut and obtain load optimization on mangrove feeders.