Improvement Of Proximity Sensor-Based Interlock System On Butterfly Valve And Danfoss Vlt Vfd Inverter To Prevent Screw Pump From Operating With The Valve Closed: Improvement sistem interlock berbasis sensor proximity pada valve butterfly dan inverter vfd danfoss vlt untuk mencegah screw pump beroperasi pada kondisi valve tertutup

Septian Putra Arifin (Program Studi Teknik Elektro, Universitas Muhammadiyah Sidoarjo)
Syamsuduhha Syahrorini (Program Studi Teknik Elektro, Universitas Muhammadiyah Sidoarjo)



Article Info

Publish Date
05 Oct 2026

Abstract

General Background Industrial piping networks utilize three-phase induction drives and isolation devices to ensure continuous and controlled fluid transfer. Specific Background Running a fluid transfer system against a closed discharge path generates trapped kinetic energy, rapidly increasing internal casing temperatures. Knowledge Gap Relying exclusively on manual observation for rotational valve positions frequently fails, causing severe mechanical failures and demanding automated, low-cost preventive solutions directly integrated into the drive control. Aims This study implements an automated inductive safety mechanism designed to block operation when the discharge path is obstructed. Results By mounting a metallic target and an inductive non-contact detector on the rotational handle, the mechanism reads the isolation device's physical orientation. This detection state is routed through a 24VDC relay directly to the variable frequency drive's push-button control line. Functional testing across three scenarios confirmed the drive was completely blocked during closed and half-open states, successfully preventing fluid entrapment and extreme heating. Novelty This system directly hardware-links an external mechanical position to a variable frequency drive's run-enable logic without requiring complex programmable controllers. Implications Deploying this straightforward, low-cost automated barrier successfully prevents severe component degradation, reduces downtime associated with human error, and secures continuous industrial workflows. Highlights: Running a fluid transfer system against a closed discharge path generates trapped kinetic energy, causing severe casing overheating. An inductive detector combined with a 24VDC relay intercepts the push-button signal to block the frequency drive. Hardware-linking mechanical isolation status directly to drive logic prevents extreme heating and component degradation. Keywords: Inductive Detector, Dead Head Prevention, Variable Frequency Drive, Preventive Maintenance, Mechanical Isolation

Copyrights © 2026






Journal Info

Abbrev

PELS

Publisher

Subject

Computer Science & IT Control & Systems Engineering Electrical & Electronics Engineering Engineering

Description

PELS (Procedia of Engineering and Life Science) is an international journal published by Faculty of Science and Technology Universitas Muhammadiyah Sidoarjo. The research article submitted to this online journal will be double blind peer-reviewed (Both reviewer and author remain anonymous to each ...