Heat transfer in cooling systems is commonly enhanced by ejector coolers, which play a crucial role in chemical industry operations. This study evaluates the performance of an ejector cooler at the ZK II Plant of PT XY through effectiveness analysis, as well as mass and energy balance assessments. Operational data were obtained over the period of 15–21 October 2025 under steady-state plant conditions. The analysis is grounded in fundamental heat transfer relations and thermodynamic principles. The results indicate that the system effectiveness varies between 72.73% and 80.15%, reflecting relatively good thermal performance under actual operating conditions. In addition, the mass balance results confirm that the system remains in equilibrium between inlet and outlet streams. From the energy analysis, the heat transfer rate ranges from 4884.65 kJ/h to 9669.62 kJ/h, showing normal operational fluctuations within the plant. Meanwhile, the mass flow rate remains fairly stable, varying from 15.57 kg/h to 19.98 kg/h. Overall, the ejector cooler demonstrates satisfactory performance in real industrial operation. These effectiveness values may serve as a useful reference for similar cooling systems. The findings also suggest that maintaining stable operating conditions is essential to ensure consistent and efficient heat transfer performance.