This Industrial Training report aims to analyze the performance of post insulators on lightning arresters (LA) and to understand their maintenance procedures at the 150 kV Cilegon Baru Substation, PT. PLN (Persero) ULTG Cilegon. The lightning arrester acts as a vital protective device to safeguard power system equipment against voltage surges caused by lightning or switching operations by diverting surge currents to the ground. The post insulator functions mechanically and electrically to support and isolate high-voltage components from the ground. The methodology involves field observation, maintenance participation, and data analysis of insulation resistance testing. The insulation resistance test results for the post insulator on phases R, S, and T were 10.6 MΩ, 2640 MΩ, and 10.2 MΩ, respectively. All measured values comply with the minimum standard requirement of 1 MΩ/kV, indicating that the equipment is in good and safe operational condition. Furthermore, maintenance procedures strictly adhere to Occupational Health and Safety (OHS) standards and Standard Operating Procedures (SOP).