Coordinated Resistive Superconducting Fault Current Limiting for Transmission-Line Current Differential Protection

Habib Muhammad Usman (King Fahd University of Petroleum and Minerals (KFUPM))
Mohammed Madhat Abualnaeem (King Fahd University of Petroleum and Minerals (KFUPM))
Forsan Hamoud Abdulmola Hassan (King Fahd University of Petroleum and Minerals (KFUPM))
Ahmed Ali Elnour Mahmoud (King Fahd University of Petroleum and Minerals (KFUPM))
Abdulrahman Al-Hashedi (King Fahd University of Petroleum and Minerals (KFUPM))



Article Info

Publish Date
19 Oct 2026

Abstract

High-resistance internal faults remain a challenging operating condition for transmission-line current differential protection because the resulting differential current may approach the relay sensitivity boundary, whereas severe through-current conditions impose stringent security requirements. This paper proposes a coordinated protection framework that integrates a resistive superconducting fault current limiter (R-SFCL) with current differential protection and evaluates the R-SFCL not only in terms of fault-current suppression, but also through its influence on the differential–restraint operating margin and high-resistance fault detectability. The proposed method couples an electrothermal R-SFCL model with synchronized terminal-current phasors and a deterministic search for the maximum detectable fault resistance. The protection performance is systematically evaluated for internal three-phase (ABC), three-phase-to-ground (ABG), phase-to-phase (AB), and single-phase-to-ground (AG) faults over aggregate R-SFCL resistances ranging from 5 to 100 Ω. Simulation results show that the R-SFCL reduces peak fault current by 31.0–41.3% while preserving dependable operation of the differential relay for all investigated internal faults under a 200-A pickup threshold and a 0.75 differential-restraint characteristic. Increasing the R-SFCL resistance also enhances high-resistance fault sensitivity. At 20 Ω, the maximum detectable fault resistances are 90, 89, 73, and 80 Ω for ABC, ABG, AB, and AG faults, respectively, increasing to limiting values of 90, 92, 73, and 83 Ω at 30 Ω or above. No further sensitivity improvement is observed beyond 30 Ω for any fault category, revealing a clear saturation in the protection benefit. These results identify an effective coordination region of 20–30 Ω, within which substantial fault-current limitation is achieved while retaining most of the attainable improvement in differential-protection sensitivity. The proposed framework therefore provides a quantitative basis for protection-aware R-SFCL sizing that balances fault-current mitigation, relay dependability, and high-resistance fault sensitivity.

Copyrights © 2026






Journal Info

Abbrev

biste

Publisher

Subject

Electrical & Electronics Engineering

Description

Buletin Ilmiah Sarjana Teknik Elektro (BISTE) adalah jurnal terbuka dan merupakan jurnal nasional yang dikelola oleh Program Studi Teknik Elektro, Fakultas Teknologi Industri, Universitas Ahmad Dahlan. BISTE merupakan Jurnal yang diperuntukkan untuk mahasiswa sarjana Teknik Elektro. Ruang lingkup ...