Battery storage in grid-connected photovoltaic (PV) systems requires dispatch rules to determine when the battery charges and discharges. This study compares three strategies Time-Based (TB), Demand-Based (DB), and TOU-Rule (TOU) using 254 days of one-minute operational PV battery load data recorded in 2019. The data were aggregated into 15-minute intervals; strategy parameters were calibrated on the first 70% of chronologically ordered days and evaluated on the remaining 30% under identical battery constraints. Energy costs were calculated using an Indonesian two-period tariff scenario based on WBP/LWBP assumptions, not the installation’s historical tariff or actual electricity bills. On test data, TOU reduced simulated energy costs by 3.17% relative to PV-only (about Rp 4,579 per day; 95% cluster-bootstrap interval based on 13 calendar segments: Rp 2,490–6,469) and raised PV self-consumption to 94.7%. DB reduced average monthly peak grid import by 10.5% but increased simulated energy costs by 9.71%. TB showed no clear cost benefit (−0.14%; its confidence interval included zero). The contribution is a controlled, data-driven comparison and a sensitivity assessment of the standby-drain assumption. Findings remain conditional on this single dataset and tariff scenario; no strategy was best for all objectives.