JTT (Jurnal Teknologi Terpadu)
Vol 6, No 2 (2018): JTT (Jurnal Teknologi Terpadu)

Analisis Keandalan Sistem Distribusi 20 KV dari GI Industri Penyulang I.5 Sampai Dengan Gardu Hubung Rapak

Tri Teguh Setiawan (UNIVERSITAS BALIKPAPAN)
A. Asni B (Universitas Balikpapan)
Bambang Sugeng (Unknown)



Article Info

Publish Date
18 Nov 2018

Abstract

The reliability of the electric power distribution system can be seen from the SAIDI number (System Average Interruption Duration Index) or long extinguished in one period and SAIFI (Sytem Average Interruption Frequency Index) or outages in one period. PT PLN (Persero) Balikpapan Area is currently trying to improve service used reliability improvement methods, namely by maneuvering the radial system network load into a loop system network and installing reclosers. Penyulang Industri 5 (I.5) for 2017 has SAIDI realization value of 7.741 hours / year, and SAIFI is 5.03 times / year. It can be interpreted that SAIDI-SAIFI 5 industrial feeders are relatively few of the value of the revised targets. This shows that industrial feeder 5 has a high level of reliability. But it still does not meet the IEEE Std standard. 1366-2000 with a SAIDI score of 2.30 hours / year and a SAIFI value of 1.45 times / year. After the improvement is obtained the value of SAIDI is almost close to the IEEE Std standard value. 1366-2000 which is 2,365 hours / year.Keywords : Reliability, SAIDI/SAIFI, Load Manuver, Recloser. 

Copyrights © 2018






Journal Info

Abbrev

jtt

Publisher

Subject

Civil Engineering, Building, Construction & Architecture Control & Systems Engineering Materials Science & Nanotechnology Mechanical Engineering

Description

JTT (Jurnal Teknologi Terpadu) dengan ISSN 2477-5177 (media online) dan 2338-6649 (media cetak), adalah jurnal ilmiah yang mempublikasikan hasil penelitian dibidang inovasi teknologi terapan dengan cakupan: Teknik Mesin, Teknik Elektro, Teknik Sipil, dan Teknik ...