INTEK: Jurnal Penelitian
Vol 3 No 2 (2016): Oktober 2016

Analisis Gangguan Tidak Seimbang pada Line Transmisi GI Sungguminasa-GI Tallasa

Marwan, Marwan (Unknown)
L, Ruslan (Unknown)
Samsul, Nur Malasari (Unknown)



Article Info

Publish Date
01 Oct 2016

Abstract

The main purpose of this research is to determine the short circuit current when there is a fault occurred on Transmission line between Sungguminasa Sub Station and Tallasa Sub Station. PT. PLN measured that the short circuit current on this transmission line is 2.8 kA. To justify the result, symmetrical component method is applied using MATLAB. The results shows that measured value from PLN is equal with the obtained results using MATLAB. This research was conducted on 19th January 2016 at 14:13 WITA.

Copyrights © 2016






Journal Info

Abbrev

Intek

Publisher

Subject

Computer Science & IT Engineering

Description

INTEK is a journal managed by the Journal and Publication Development Unit of Ujung Pandang State Polytechnic, which is published twice a year, in April and October. The journal INTEK has also been indexed. The INTEK Journal accepts research scripts in the fields of technology and engineering such ...