Co-optimization of capacitor placement and generator voltage control using advanced BFOA for active power loss reduction under extreme load levels Anh Tuan Bui; Tien Dung Nguyen; Tung Tran
Indonesian Journal of Electrical Engineering and Computer Science Vol 44, No 1: October 2026
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v44.i1.pp9-21

Abstract

Optimal reactive power dispatch (ORPD) is a critical tool for maintaining the efficiency and security of modern power systems. This paper addresses the ORPD problem under highly stressed grid conditions (130% loading) by proposing a comprehensive co-optimization framework. The framework simultaneously optimizes discrete shunt capacitor capacities and continuous generator terminal voltages using an advanced bacterial foraging optimization algorithm (BFOA) integrated with a time-varying dynamic step-size strategy. The methodology is validated on the IEEE 14-bus system and compared against standard particle swarm optimization (PSO). Simulation results demonstrate that the proposed BFOA achieves a superior active power loss reduction of 23.502% (from 28.067 MW to 21.470 MW) and effectively eliminates all generator reactive power (Qg) violations. The findings highlight the importance of joint co-optimization in achieving global grid efficiency under extreme operational scenarios.