Analisis Pengujian dan Lifetime Pemutus Tenaga 150 kV di Gas Insulated Switchgear Karang Pilang Misbahul Munir; Mochammad Akbar Mulyono; Wahyu Setyo Pambudi; Yuliyanto Agung Prabowo; Novian Patria Uman Putra; Titiek Suheta
Journal Renewable Energy, Electronics and Control Vol 6, No 2 (2026): JREEC : Journal of Renewable Energy, Electronics and Control
Publisher : Department of Electrical Engineering, Institut Teknologi Adhi Tama Surabaya

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31284/j.jreec.2026.v6i2.9407

Abstract

Pemutus Tenaga (PMT) memerlukan evaluasi berkala karena operasi switching dan penurunan isolasi dapat memengaruhi keandalan pelayanan. Penelitian ini mengevaluasi PMT 150 kV Rungkut 1 dan Rungkut 2 di GIS Karang Pilang menggunakan tahanan isolasi, kontak, dan pentanahan, keserempakan kontak, kemurnian SF6, serta histori trip 2020–2024. Kemurnian SF6 dilaporkan 99,9%, sedangkan waktu operasi kontak berada di bawah 120 ms. Model regresi yang dilaporkan memproyeksikan 2.051 trip pada 2052 untuk Rungkut 1 dan 2.071 trip pada 2051 untuk Rungkut 2 terhadap ambang 2.000 trip. Data sumber mendukung hasil keserempakan dan SF6, tetapi interpretasi tahanan kontak, ekstrapolasi Rungkut 2, dan validasi mengandung inkonsistensi yang memerlukan konfirmasi penulis sebelum pengajuan.