Ahmad Ilham Kamal Pemanfaatan Hall Effect untuk Mendeteksi Kebocoran Arus pada Beban Cabang Sistem DC Menggunakan Metode Beda Arus Positif-negatif Kamal, Ahmad ilham; Dona, Nur Rahma
Journal of Energy, Material, and Instrumentation Technology Vol 6 No 2 (2025): Journal of Energy, Material, and Instrumentation Technology
Publisher : Departement of Physics, Faculty of Mathematics and Natural Sciences, University of Lampung

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.23960/jemit.v6i2.232

Abstract

Currently, many industries use DC power as a power supply for controller equipment, etc. All companies want their DC system to be reliable. One effort to maintain the reliability of the DC system is to monitor the leakage current in each branch of the DC system load. Leakage currents that occur if not discovered early on will gradually result in short circuit currents and instability of the DC system. This research wants to use the hall effect to detect leakage currents in branch loads using the difference in current in the positive (+) and negative (-) cables. Use the right-hand law for the direction of the magnetic field. Insert the positive (+) and negative (-) cables into the same Hall sensor where the resultant magnetic field will be 0 under normal circumstances and >0 or <0 if there is a leakage current in one of the cables. Because of this, the Hall effect can be used to detect leakage currents (Ground Fault) in DC systems. Another advantage of the Hall effect is that it monitors DC system leakage currents continuously while operating.