A Study of SVC’s Impact Simulation and Analysis for Distance Protection Relay on Transmission Lines Ngo Minh Khoa; Nguyen Huu Hieu; Dinh Thanh Viet
International Journal of Electrical and Computer Engineering (IJECE) Vol 7, No 4: August 2017
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (711.125 KB) | DOI: 10.11591/ijece.v7i4.pp1686-1695

Abstract

This paper focuses on analyzing and evaluating impact of a Static Var Compensator (SVC) on the measured impedance at distance protection relay location on power transmission lines. The measured impedance at the relay location when a fault occurs on the line is determined by using voltage and current signals from voltage and current transformers at the relay and the type of fault occurred on the line. The MHO characteristic is applied to analyze impact of SVC on the distance protection relay. Based on the theory, the authors in this paper develop a simulation program on Matlab/Simulink software to analyze impact of SVC on the distance protection relay. In the power system model, it is supposed that the SVC is located at mid-point of the transmission line to study impact of SVC on the distance relay. The simulation results show that SVC will impact on the measured impedance at the relay when the fault occurs after the location of the SVC on the power transmission line.