Claim Missing Document
Check
Articles

Found 3 Documents
Search

Enhanced dynamic performance of grid feeding distributed generation under variable grid inductance Salman Harasis; Saher Albatran; Eyad Almaita; Khaled Alzaareer; Qusay Salem; Mamdouh Alghaythi; Mohammad Arifur Rahman
International Journal of Electrical and Computer Engineering (IJECE) Vol 12, No 2: April 2022
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijece.v12i2.pp1113-1122

Abstract

Controlling weak grid-connected systems is very challenging. In transient, frequency and voltage oscillations may lead to voltage and/or frequency stability problems and finally lead to system collapse. During steady-state operation and at the point of common coupling (PCC), voltage degradation and grid voltage background harmonics restrict the inverter's functionality, reduce the power flow capability and cause poor power quality. With weak grid connection, grid impedance variance will contaminate the voltage waveform by harmonics and augment the resonance, destabilizing the inverter operation. In this paper, complete mathematical modeling is carried out and state feedback-plus-integral control is implemented to support the stabilization of the system. The proposed controller is adopted to provide a smooth transient under sudden load change by controlling the injected grid current under different grid inductance values. Furthermore, the proposed control is used to reduce the order and size of the inverter output filter while maintaining system stability. The proposed control has been compared with the conventional proportional integral (PI) controller under different scenarios to validate its effectiveness and to strengthen its implementation as a simple controller for distributed generator applications.
A performance comparison of series power flow control structures in a smart microgrid Qusay Salem; Khaled Alzaareer; Salman Harasis
International Journal of Power Electronics and Drive Systems (IJPEDS) Vol 13, No 2: June 2022
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijpeds.v13.i2.pp908-917

Abstract

This paper investigates the performance of various power control structures on a series power flow controller comprised as transformerless H-bridge inverter under different operating conditions. This power flow controller connects the main grid with the microgrid as it is seriesly attached with the distribution line. Three different control strategies are implemented to regulate the power flow at the interface point using the series power flow controller. The feasibility of the regulation approaches is verified by varying the modulation index and the reference DC-link voltage during different operation modes. Also, the performance of the control strategies is verified under load divergence condition during two different operation modes. The results showed the efficacy of the developed regulation methods in injecting series voltage at point of common coupling (PCC) either during the capacitive or the inductive operation mode. Also, the obtained results reveal the stability and reliability of the regulation methods and the microgrid operation when either the reference DC-link voltage or the modulation index are increased.
Sensitivity analysis of voltage limit in radial AC microgrids considering the loading condition and line length Qusay Salem; Rafat Aljarrah
Bulletin of Electrical Engineering and Informatics Vol 15, No 5: October 2026
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/eei.v15i5.11620

Abstract

A sensitivity analysis of voltage compliance in radial AC microgrids linked to a low-voltage main grid is presented in this paper, with an emphasis on the combined effects of feeder length and load-generation balance. Three loading scenarios: demand exceeding generation, demand matching generation, and generation exceeding demand are used to apply a Newton-Raphson power flow algorithm to a radial network with five distributed generators (DGs) and five loads. Feeder lengths, both long and short, are assessed for every condition. The findings indicate that voltage falls below the IEEE 1547 lower limit of 207 V when demand exceeds generation with long feeders (200 m line sections), falling as low as 166.9 V at the farthest load, potentially causing load shedding and DG disconnection. On the other hand, even in extended feeder situations, voltages stay within the acceptable ±10% range when generation matches or surpasses demand. These results offer useful recommendations for feeder design and DG placement in grid-connected microgrids, as well as quantitative insights into worst-case operation scenarios.