Power Transformer Incipient Faults Diagnosis Based on Dissolved Gas Analysis Osama E. Gouda; Saber M. Saleh; Salah Hamdy EL-Hoshy
Indonesian Journal of Electrical Engineering and Computer Science Vol 16, No 3: December 2015
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v16.i3.pp409-416

Abstract

Incipient fault diagnosis of a power transformer is greatly influenced by the condition assessment of its insulation system oil and/or paper insulation. Dissolved gas-in-oil analysis (DGA) is one of the most powerfull techniques for the detection of incipient fault condition within oil-immersed transformers. The transformer data has been analyzed using key gases, Doernenburg, Roger, IEC and Duval triangle techniques. This paper introduce a MATLAB program to help in unification DGA interpretation techniques to investigate the accuracy of these techniques in interpreting the transformer condition and to provide the best suggestion for the type of the fault within the transformer based on fault percentage. It proposes a proper maintenance action based on DGA results which is useful for planning an appropriate maintenance strategy to keep the power transformer in acceptable condition. The evaluation is carried out on DGA data obtained from 352 oil samples has been summarized into 46 samples that have been collected from a 38 different transformers of different rating and different life span.
Improving the power factor correction in the presence of harmonics by reducing the effect of resonance and harmonics Saber M. Saleh; Mohamed E. Arafa
Indonesian Journal of Electrical Engineering and Computer Science Vol 3, No 2: August 2016
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v3.i2.pp282-295

Abstract

Harmonics in electrical networks occur as a result of non-linear loads.  It has an effect on power factor improvement using capacitors in terms of increasing the unbalance current between units. In addition, the occurrence of resonance and result in the exit of capacitors from service by the protective relays to protect the units from collapse. The main objective of this research is the real-time study of improving the power factor with reducing the effect of the resonance and harmonics on the power system. This reduction can be done using filters, consist of reactors and capacitors connected in series or in parallel or series and parallel together to reduce the current harmonics or voltage harmonics. Single Tuned filter type (passive filter) is used which presents very low impedance at the tuning frequency, through which all current of that particular frequency will be diverted. This research presents two practical power systems 11kV source in Fayoum substation and 13.8kV source in New Badr substation connected to power factor Improvement circuit. These models simulated by Matlab at different unbalance currents and harmonics. Also, it presents the design of the series reactor and the harmonics filter which satisfy the minimum effect of resonance and harmonics.
Notice of Retraction Power Transformer Incipient Faults Diagnosis Based on Dissolved Gas Analysis Osama E. Gouda; Saber M. Saleh; Salah Hamdy El-hoshy
Indonesian Journal of Electrical Engineering and Computer Science Vol 1, No 1: January 2016
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v1.i1.pp10-16

Abstract

Notice of Retraction-----------------------------------------------------------------------After careful and considered review of the content of this paper by a duly constituted expert committee, this paper has been found to be in violation of IAES's Publication Principles.We hereby retract the content of this paper. Reasonable effort should be made to remove all past references to this paper.The presenting author of this paper has the option to appeal this decision by contacting info@iaesjournal.com.-----------------------------------------------------------------------Incipient fault diagnosis of a power transformer is greatly influenced by the condition assessment of its insulation system oil and/or paper insulation. Dissolved gas-in-oil analysis (DGA) is one of the most powerfull techniques for the detection of incipient fault condition within oil-immersed transformers. The transformer data has been analyzed using key gases, Doernenburg, Roger, IEC and Duval triangle techniques. This paper introduce a MATLAB program to help in unification DGA interpretation techniques to investigate the accuracy of these techniques in interpreting the transformer condition and to provide the best suggestion for the type of the fault within the transformer based on fault percentage. It proposes a proper maintenance action based on DGA results which is useful for planning an appropriate maintenance strategy to keep the power transformer in acceptable condition. The evaluation is carried out on DGA data obtained from 352 oil samples has been summarized  into 46 samples that have been collected from a 38 different transformers of different rating and different life span.