JURNAL NASIONAL TEKNIK ELEKTRO
Vol 8, No 2: July 2019

Migration Between Two Inverse Time-Overcurrent Curves of Different Standard: Experience at Siguragura Power Station

Gautama, Bagus Brahmantya (PT Indonesia Asahan Aluminium (Persero))



Article Info

Publish Date
11 Jun 2019

Abstract

The inevitable replacement of electro-mechanical protection relays with more recently-developed microprocessor-based protection relays poses challenges to engineer, one of which is migration from existing manufacturer’s non-standard inverse time-overcurrent curve to, usually, IEC 60255-151 or IEEE Std C37.112-1996 curve. To satisfy the required protection coordination, one may perform new study of protection coordination for the system in total, prior to replacement program. However, this exhaustive approach can be avoided by emulating existing non-standard inverse time overcurrent curve on the new microprocessor-based protection relay, provided that such curve is still adequate to be re-implemented. This paper aims to develop general procedure using nonlinear curve fitting to determine the most appropriate setting of microprocessor-based protection relay. The general procedure has been tested during renewal of feeder protection relay at Siguragura Power Station.

Copyrights © 2019






Journal Info

Abbrev

JNTE

Publisher

Subject

Electrical & Electronics Engineering

Description

Jurnal Nasional Teknik Elektro (JNTE) adalah jurnal ilmiah peer-reviewed yang diterbitkan oleh Jurusan Teknik Elektro Universitas Andalas dengan versi cetak (p-ISSN:2302-2949) dan versi elektronik (e-ISSN:2407-7267). JNTE terbit dua kali dalam setahun untuk naskah hasil/bagian penelitian yang ...