Jurnal Energi Dan Manufaktur
Vol 3, No.1 April 2009

Testing of Model Water Chiller System with Hidrokarbon as a Primer Refrigeran

Nengah Suarnadwipa (Unknown)
Ketut Astawa (Unknown)



Article Info

Publish Date
08 Nov 2012

Abstract

Now days, there are two issues that give a negative impact on the environment due to the uses of synthetic refrigerant on therefrigeration system and air conditioning system. The first issue was the Ozon Layer Depletion and the second issue was theGlobal Warming. Regarding those condition, it will be investigated the design and examination of performance the use of thesplit type AC system as water chiller system and using hydrocarbon as a primer refrigerant. As a result, in the examination ofthe standard split type AC system using refrigerant R-22, it founded that the cooling rate of 1958 Watt and COP of 5.29.While the examination on the modified split type AC system into water chiller system using hydrocarbon (hycool 22), hasgiven cooling rate of 1832 Watt and COP of 4.19. Finally, it could be councluded that the split type AC system could be usedas water chiller system.

Copyrights © 2009






Journal Info

Abbrev

jem

Publisher

Subject

Energy Industrial & Manufacturing Engineering

Description

"Jurnal Energi dan Manufaktur" is a journal published by Department of Mechanical Engineering, University of Udayana, Bali since 2006. During 2006-2011 the journal's name was "Jurnal Ilmiah Teknik Mesin CAKRAM" (Scientific journal in mechanical engineering, CAKRAM). "Jurnal Energi dan Manufaktur" is ...