Jurnal SPEKTRUM
Vol 5 No 1 (2018): Jurnal SPEKTRUM

Studi Pengaruh Jenis Refrigerant Terhadap Pemakaian Daya Listrik Pada Mesin Pengkondisian Udara (AC)

I Nyoman Mudana (Unknown)
Yanu Prapto Sudarmojo (Unknown)
I Gusti Ngurah Janardana (Unknown)



Article Info

Publish Date
25 Jun 2018

Abstract

Air conditioning is strongly influenced by Refrigerant. R.22 refrigerant is currently still widely used with high level of electric power consumption. The purpose of this research is to analyze the influence of types of refrigerant to the electric power consumption of AC by measuring the electric power requirement of each Refrigerant (R.22, R.410, R.32, EnggasM60 and Isceon MO99). The results showed that R.410 uses 335 Watt with the total cost of Rp 42,210 / month, R.32 uses 328 Watt power with the total cost of Rp 41.328 / month, R.22 uses 271 Watt power with theotal cost of Rp 34.146 / month, Huffin M60 uses 262 Watt power with the total cost of Rp 33.012 / month. While Isceon M099 requires 262 Watt with the total cost of Rp 33.012 / month at the temperature of 24,4 ° C.

Copyrights © 2018






Journal Info

Abbrev

spektrum

Publisher

Subject

Computer Science & IT Electrical & Electronics Engineering Energy Engineering Industrial & Manufacturing Engineering

Description

Jurnal SPEKTRUM is peer review journal, published four times a year by the Department of Electrical Engineering, Faculty of Engineering, Universitas Udayana. This journal discusses the scientific works containing results of research in the field of electrical, include: power systems, ...