Large motors often burden synchronous generators as power plants in factories. This motor is commonly using to regulate rotation using Variable Speed Drive (VSD). From the load side, VSD, as a regulator of motor rotation, can reduce power loss. On the generator side as a power plant, this load with VSD affects the waveform of the generator. The experiments on a small capacity generator (6 kVA) with a VSD as regulating the motor rotation with a load of about 1.1 kW shows effectiveness power transfer is about 40.7% with VSD, and without VSD, efficiency is approximately 39.6%. The motor losses by installing VSD interpreted as transferring losses to the generator with savings is about 1 %. The experiments also showed that generator performance decreases when loaded with VSD at around 6%, and a generator temperature increases at 20 0C higher than without VSD.