Analisis Kedip Tegangan Pada Trafo Distribusi 20 KV Fakultas Teknik Universitas Riau Menggunakan Power Quality Analyzer (PQA)

Riko Simalango (Unknown)
Firdaus Firdaus (Unknown)



Article Info

Publish Date
21 Sep 2020

Abstract

The voltage dip is a disturbance that often occurs in electrical power systems that reduce power quality. In general the voltage dip appear from the use of electrical equipment and electrical machines that consume a lot of power, and will be effect the performance of electronic and sensitive equipments caused by voltage dip. Voltage dip measurement in a 20kV distribution transformer of Engineering Faculty Riau University will be compared with IEEE 1159-1995 Standard. The method use in this research is a direct measurement using Power Quality Analyzer (PQA) KEW 6310 for each phase of the transformer. From the results of measurements from October 21 - October 28, 2019 phase R on Monday, October 21, 2019 At 15:05 WIB voltage dip occurred for 0,2 seconds, the voltage drop was 24,4 volts (10,16%), phase S on Thursday, October 24, 2019 at 15:48 WIB, there was a voltage dip of 25,1 volts (25,1%) for 0,2 second, voltage dip in measurements that have been made a long time the dip category momentary, and phase T are not experiencing a voltage dip, the voltage drop was 10,8 volts (4,50%). Keywords: voltage dip, distribution transformer, power quality analyzer (pqa)