ANALISIS PENGARUH CLEANING TUBING KONDENSOR TERHADAP PERFORMA SISTEM REFRIGERASI MESIN WATER COOLED CHILLER KAPASITAS 650TR

Agung Pranoto (Universitas Ibn Khaldun Bogor)
Hablinur Al Kindi (Universitas Ibn Khaldun Bogor)
Gatot Eka Pramono (Universitas Ibn Khaldun Bogor)



Article Info

Publish Date
29 May 2023

Abstract

The condenser needs to be cleaned so that the performance of the heat exchanger can optimally. This research was conducted on a water cooled chiller machine with a capacity of 650TR and the type of refrigerant used is R134a to determine the performance of the machine after cleaning process. The electric power used by the compressor’s motor before there was a fouling, fouling and after cleaning the condenser tubing were 174,80 kW, 191,22 kW and 174,42 kW respectively. The mass flow rate of cooling water before there is a fouling, fouling and after cleaning the condenser tubing is 98,01 kg/s, 106,74 kg/s and 126,15 kg/s respectively. The actual cooling load before there is a fouling, fouling and after cleaning the condenser tubing is 1352,46 kW, 1343,27 kW and 1363,92 kW respectively. Heat rejected before there is a fouling, fouling and after cleaning the condenser tubing is 1527,26 kW, 1534,49 kW and 1538,34 kW respectively. Coefficient of performance heating before there is a fouling, fouling and after cleaning the condenser tubing is 8,75, 8,04 and 8,82 respectively. Based on the results of the research, the performance of the water cooled chiller machine has increased after cleaning the condenser tubing.

Copyrights © 2023






Journal Info

Abbrev

rm

Publisher

Subject

Mechanical Engineering

Description

Rekayasa Mesin is published by Mechanical Engineering Department, Faculty of Engineering, Brawijaya, Malang-East Java-Indonesia. Rekayasa Mesin is an open-access peer reviewed journal that mediates the dissemination of academicians, researchers, and practitioners in mechanical engineering. Rekayasa ...