Fluctuations in electricity demand can lead to inefficiencies in diesel generators (DEG) and potentially trigger blackouts, as experienced by PT Indolakto. This study aims to identify the performance parameters of a 2 MW DEG and formulate strategies to prevent blackouts caused by the 2 MW DEG at PT Indolakto. The research used data collection techniques including field observations, interviews, literature studies, and performance test analysis. The results showed that the efficiency of the 2 MW DEG at load reached 44%, indicating there is still reserve power. An overload of 21% from the generator's capacity resulted in a blackout and a system frequency drop of 13.4 Hz from the normal frequency. Although the 2 MW DEG has adequate efficiency, optimization is necessary to prevent blackouts. One strategy is to use the 2 MW DEG as a system reserve for critical loads.