Analysis Of Distribution Transformer Shifting To Address Overload And End Voltage At Gardu HJ177 In PT. PLN (Persero) Kertosono Service Unit

Tri Della Cristy Sembiring (Unknown)
Dicky Lesmana (Unknown)
Yoffi Andinata (Unknown)



Article Info

Publish Date
26 Aug 2024

Abstract

The HJ177 substaion in its loading datareached 126.10% (± 63,054 kVA) of its capacity of 50 kVAwith an end voltaicge of 206 V and experienced avoltage dropge of 12%. The loading exceeded the maximum capacity of the stanord transformer of 80%, which has the potential for materialand finalncial losses for PT PLN (Persero) Kertosono Customer Service Unit (ULP). The voltalge drop resulting from this has exceeded SPLNT6.001-2013 of -±10% for low voltagege. Considering the matrix in the Health Index aassessment tier-1 Distribution Transformer, willingted to the percentage of tranformer loading, it's in the bald caBeca's categoryuse it is loaded ≥100%. To overcome this, an insert transformer caln be installed. With the originl load from 126.10% to 46.942% of the 50kVAcapacity, then the end voltage at the HJ177 Substation with the insertion of the transformer was originallly 206 V with avoltage drop of 12.0% increased to 213 V with avoltage drop percentage that decreased to 8.2%. The implementation of the transformer insertion for the HJ177 substation is effective in overcoming overloadyesnd improving the end voltage

Copyrights © 2024






Journal Info

Abbrev

pendidikan

Publisher

Subject

Education Mathematics

Description

Scientific Journal is a publication by Sean Institute, which is devoted to the field of education with the topic of Learning Effectiveness studies, Analysis of Learning Influences, Application of Learning Models and the development of instructional media; we also invite the teachers, researchers, ...