Building heating, ventilation, and air conditioning (HVAC) systems are among the most critical facilities with the most significant energy consumption. This article is based on the issues faced by PT X regarding the importance of visual analytics in energy audits and the performance evaluation of water-cooled chillers and cooling towers. The research methodology used is descriptive qualitative with a quantitative approach, where primary data is obtained based on observations of the machines owned by PT X. The approach taken involves the application of spreadsheets as a system for processing operational data and Looker Studio for real-time data visualization, aimed at understanding performance and energy consumption. The research results show that visualization with the Looker Studio platform provides a solution for PT X to improve the efficiency and effectiveness of the company's performance. In addition, the analysis conducted over six months on the coefficient of performance of a 2,000 TR water-cooled chiller showed a highest value of 21.5 and a lowest value of 13.31, while the highest efficiency of the cooling tower reached 98% and the lowest was 74%.