Abstract

Loading that exceeds the capacity of the transformer if left unchecked will damage the transformer itself; apart from that, it can also cause drop voltage along the conductor, which causes electricity services to customers to be disrupted, especially at the customer end. The results of research at PT PLN (Persero) ULP 50 Kota Suliki Service Office revealed that of the 108 existing transformers, the GD 175 Kasiak Rampung transformer experienced overload with a percentage of 99%, and the end voltage measurement was 177 volts. This figure does not comply with the standards set by PLN. An insert transformer was built as an improvement effort so that the loading percentage decreased to 45% and the end voltage became 277 volts. This effort provides benefits, namely improving the quality of customer service, increasing electricity sales, reducing ENS if there are maintenance efforts, and improving the company's image.

Copyrights © 2024






Journal Info

Abbrev

jiaee

Publisher

Subject

Control & Systems Engineering Electrical & Electronics Engineering Energy Engineering

Description

Journal of Industrial Automation and Electrical Engineering (JIAEE) is an open-access peer-reviewed journal which is providing a platform to researchers, scientists, engineers, and practitioners/professionals throughout the world to publish the latest creations and achievement, future challenges and ...