Understanding the response of power systems to symmetrical faults is essential for maintaining electricity supply reliability and operational stability. This study investigates the responses of a three-phase symmetrical fault at the primary and secondary sides of an 11 kV/415 V transformer using MATLAB/Simulink. The simulated power system consists of three 11 kV, 10 MVA, 50 Hz voltage sources connected to a 10 MVA, 11 kV/415 V delta-wye transformer supplying a load of 2 MW active power and 10 kVAR reactive power. Three-phase symmetrical disturbances are introduced at different locations to evaluate their effects on system voltage and current responses. The simulation results demonstrate that symmetrical disturbances produce different voltage and current variations depending on the fault location relative to the transformer. The comparative analysis provides insight into the influence of transformer-side fault locations on power system responses. These findings contribute to a better understanding of symmetrical fault characteristics and provide a basis for evaluating power system protection and disturbance management strategies.