JUVOTEK JURNAL: Jurnal Vokasi Teknik
Vol 4 No 02 (2026): July ISSUE | JUVOTEK JURNAL

Menentukan Drop tegangan pada Distribusi daya dari Generator ke motor Induksi tiga Fhasa disebabkan Panjang kabel penghantar unit screw press PTPN II Sawit Hulu

Bayu Hillam Saputra Tambunan (Fakultas sains dan teknologi, Universitas Tjut Nyak Dhien, Indonesia.)
Mulia Mulia (Fakultas sains dan teknologi, Universitas Tjut Nyak Dhien, Indonesia.)
Supriadi Supriadi (Fakultas sains dan teknologi, Universitas Tjut Nyak Dhien, Indonesia.)



Article Info

Publish Date
18 Apr 2026

Abstract

Voltage drop is the amount of voltage lost in a conductor. The voltage drop on electric power lines is generally directly proportional to the length of the line and the load and inversely proportional to the cross-sectional area of the conductor. The magnitude of the voltage drop is expressed either in percent or in Volts. The analysis determines the voltage drop in the power distribution from the generator to the three-phase induction motor at PT. PERKEBUNAN NUSANTARA II Sawit Hulu uses 30 meters of copper conductor cable with a cross-sectional area of 400 mm2. This type of copper wire material with an absolute value of sending voltage of 389 volts and an absolute value of receiving voltage of 385 volts. So that there is a voltage drop based on the length of the conducting cable of 4 Volts. And if it is percentaged, the voltage drop value is 1.03%.

Copyrights © 2026






Journal Info

Abbrev

juvotek

Publisher

Subject

Chemical Engineering, Chemistry & Bioengineering Computer Science & IT Electrical & Electronics Engineering Industrial & Manufacturing Engineering Mechanical Engineering

Description

JUVOTEK JURNAL: Jurnal Vokasi Teknik (JuVoTek) is a peer-reviewed, open-access scientific journal that publishes original and high-quality research in vocational engineering, applied technology, and multidisciplinary engineering studies. The journal provides an academic platform for researchers, ...