Electrical energy is essential for supporting the operational activities of commercial buildings. Fitness centers have relatively high electricity consumption due to the use of air conditioning (AC), lighting, sports equipment, and other electrical devices that operate for long hours. LPD GYM Pemogan was selected as the study object because it operates daily with extended hours and various electrical loads. This study aims to determine the Energy Consumption Intensity (ECI), evaluate electrical energy use by comparing the ECI with applicable standards, and identify Energy Saving Opportunities (ESO). The research uses a quantitative descriptive method with an initial energy audit approach, using primary and secondary data on building conditions, electrical equipment, installed power capacity, building area, operating hours, electricity consumption, and electricity bills over six months. The analysis was conducted by calculating electricity consumption and ECI and comparing the results with reference standards. The average electricity consumption was 14,850 kWh/month, with a building area of 764.62 m². The ECI was 19.42 kWh/m²/month or 233.06 kWh/m²/year. Based on the ECI standard for air-conditioned buildings, the value is categorized as inefficient (wasteful), while it remains below the ASEAN-USAID benchmark. Energy savings can be achieved by optimizing AC temperature set points, regulating AC operation, and adjusting schedules according to room usage.