This study develops an Internet of Things (IoT)-based monitoring system for a parking-building lighting control panel supplied by a 1.65 kWp photovoltaic system with a hybrid PV-grid source. The system integrates an ESP32, PZEM-004T for AC measurement, PZEM-017 for battery-side DC measurement, a 20×4 LCD, Wi-Fi, MQTT, and a web dashboard. Field testing was conducted for five days by comparing voltage and current readings with an AVO meter and clamp meter and by observing battery operation and source transfer. The reported average errors were 0.18% for AC voltage, 0.02% for AC current, 0.09% for DC voltage, and 0.045% for DC current. The measured data were displayed on the LCD and dashboard, and a transfer from the battery to the PLN grid was observed at the end of the discharge scenario. Network latency and packet loss, ATS transfer time, SOC validation, and independent power-meter validation were not measured. The results support the use of the ESP32-PZEM-MQTT architecture as a functional monitoring layer for a PV-powered lighting panel, while the conclusions remain limited to the tested operating conditions.