The installation of a rotameter measuring instrument was designed as an aid for practical sessions in the refrigeration system installation course due to the limited equipment available in the basic refrigeration laboratory of the Department of Refrigeration and Air Conditioning Engineering at Politeknik Negeri Bandung. This study aims to design, install, and evaluate the performance of a rotameter on a refrigeration system trainer unit. Refrigerant charging into the trainer unit uses a rotameter to measure and control the fluid flow rate. The effect on the refrigeration system trainer unit is then observed. There are three types of refrigerant flow variations, namely using rotameters with capacities of 120 grams (18 L/min), 220 grams (21 L/min), and 350 grams (25 L/min). Measurements were conducted for 110 minutes or until the system reached a steady state. Using CoolPack software, it was found that the COP (Coefficient of Performance) value for the 120-gram variation was only 2.54, while for the 220-gram variation, it was 4.19, and for the 350-gram variation, it reached 4.74. Higher refrigerant charging variations also resulted in an increase in the COP, where a higher COP value indicates more efficient performance.