Cold storage is a low-temperature storage facility that plays a crucial role in maintaining product quality within the food industry and modern commerce. The refrigeration system in this facility utilizes R404A refrigerant, a replacement for the original R22 refrigerant; yet, to date, no specific study has been conducted on the system's Coefficient of Performance (COP). Measurements and analysis indicate a refrigeration effect of 100.2 kJ/kg and a compressor work input of 65.5 kJ/kg. Although the COP value suggests that the system is capable of performing its cooling function effectively (maintaining a temperature of −20 °C), it is not yet operating optimally. An analysis of operational parameters shows that the superheat on the suction side (9.1 °C) and the evaporator air temperature differential (4.8 °C) remain within the normal range. However, a subcooling value in the liquid line approaching 0 °C suggests that the refrigerant retrofit process—from R22 to R404A—has not been fully optimized, particularly regarding the refrigerant charge quantity and the compatibility of the lubricating oil. This is believed to be one of the factors contributing to the system's suboptimal COP.