Variable Speed Drives (VSDs) are widely used to regulate the speed of three-phase induction motors in industrial applications. However, as nonlinear loads, VSDs generate current and voltage harmonics due to the switching processes in their rectifier and inverter circuits. This study analyzes the harmonics generated by a VSD in a three-phase induction motor (81-SML2-1) driving a belt conveyor at PT Pupuk Iskandar Muda, with specifications of 5.5 kW, 380 V, four poles, 1,175 rpm, and a frequency of 39 Hz. It also evaluates the effectiveness of passive single-tuned filters in mitigating these harmonics. Simulations were conducted using MATLAB Simulink R2024b under constant-load and dynamic-load conditions (torque ranging from 5 to 25 Nm), with FFT analysis performed using Powergui based on IEEE 519-2022. Before filter installation, the THDi reached 20.25% and the THDv reached 161.24% under constant-load conditions, while under dynamic-load conditions, the THDi and THDv reached 26.59% and 164.82%, respectively. Three single-tuned filters tuned to the 3rd, 4th, and 11th harmonic orders and installed at the inverter output side reduced the THDi to 1.19% and the THDv to 5.29% under constant-load conditions, as well as reduced the THDi to 1.01% and the THDv to 5.54% under dynamic-load conditions. The reduction effectiveness ranged from 94% to 97%, bringing the THDv below the 8% limit. Variations in the number of filters showed that using only one or two filters was insufficient to suppress all dominant harmonic orders. Furthermore, a single 11th-order filter and a combination of 4th- and 11th-order filters increased distortion under dynamic-load conditions.