In boarding schools with separate wastewater treatment units, total bed capacity alone does not indicate which unit will experience the highest hydraulic load. This study evaluated whether each unit's reported treatment capacity at a boarding school in North Toraja, Indonesia, could accommodate the average daily inflow at full occupancy. The analysis considered the school’s 720 residential places, including 400 in the girls’ dormitory and 320 in the boys’ dormitory. A water balance approach allocated wastewater from each activity to its respective unit using activity-specific water allowances and wastewater return fractions. Estimated wastewater generation was 45.504 m³/day, exceeding the combined reported capacity of 35 m³/day by 10.504 m³/day. Both the girls’ and boys’ dormitory units had a reported capacity of 15 m³/day, but their estimated inflows were 22.400 and 17.920 m³/day, respectively. The girls’ unit represented 70.4% of the total projected shortfall. At the shared laundry and kitchen unit, the estimated inflow exceeded capacity by only 0.184 m³/day, and the assessment outcome changed when the assumed return fraction decreased from 80.0% to approximately 77.2%. Linking occupancy and water use to individual units identified the girls’ dormitory as the priority for verifying treatment capacity and measuring inflow.