ANALYSIS OF AIR-COOLED CONDENSER EFFECTIVENESS UNDER TROPICAL AMBIENT TEMPERATURE VARIATIONS IN LOW-ENTHALPY GEOTHERMAL SYSTEMS Richard Alexander; Agus Setyawan; Udi Harmoko
Trends in Mechanical Engineering Research Vol 4, No 1 (2026): JUNE
Publisher : Department of Mechanical Engineering, Universitas Sultan Ageng Tirtayasa

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.62870/timer.v4i1.40713

Abstract

The performance of Air-Cooled Condensers (ACC) in low-enthalpy geothermal systems is strongly influenced by ambient temperature as the primary cooling medium. This study analyzes the effect of tropical ambient temperature variations on ACC effectiveness using the effectiveness-NTU method and linear regression based on 1,415 operational data points. The results show that the calculated ACC effectiveness ranges from 49.93% to 64.46% within an ambient temperature range of 18.63°C to 29.56°C. Ambient temperature shows a very strong positive correlation with ACC effectiveness, with r = 0.9984 and R² = 0.9967. The increase in effectiveness at higher ambient temperatures is associated with a reduction in the theoretical maximum heat transfer rate (Qmax), rather than an improvement in actual cooling performance. The developed model can be used as a simple predictive tool for operational management of low-enthalpy geothermal systems in tropical regions.
Ambient-Temperature Sensitivity of Operating-Data Fouling-Resistance Indicators for an Air-Cooled Condenser in a Binary Geothermal Power Plant Richard Alexander; Agus Setyawan; Udi Harmoko
International Journal of Innovation in Mechanical Engineering and Advanced Materials Vol. 8 No. 3 (2026)
Publisher : Universitas Mercu Buana

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.22441/ijimeam.v8i3.40219

Abstract

Air-cooled condensers (ACCs) reject heat directly to the atmosphere, so operating-data fouling indicators are read against a heat sink that moves continuously. This study quantifies how much of the calculated fouling resistance of an ACC serving a 41.75 MW binary geothermal unit is generated by ambient-temperature variation alone, with the physical surface condition held unchanged, and establishes how that component depends on whether cooling-air flow is measured or inferred. A zone-resolved thermal model was built from bundle geometry, plant working-fluid states and a measured fan air velocity of 6.02 m s⁻¹, with n-pentane and air properties taken from CoolProp. The indicator was evaluated over the observed ambient range of 18.63 to 29.56 °C under three routes that differ only in which air-side quantity is measured. Ambient variation alone moved the indicator by 2.22 × 10⁻² m² K W⁻¹ across the mean daily range, which exceeded its own mean value by a factor of 3.3 and reversed its sign at 24.5 °C although the surface condition did not change. The negative values carry no physical meaning, because a deposit cannot reduce thermal resistance. The sign of the reported trend followed the air-side assumption rather than the equipment, and four clean-condition treatments shifted the level of the indicator without altering its ambient slope, which stayed negative in 100 % of 2,000 Monte Carlo samples. The calculated resistance therefore measures the ambient sensitivity of the method and not the fouling state of the bundle. Matched-ambient comparison bands, a plant-specific clean baseline and independent air-side indicators are required before it can support a cleaning or maintenance decision.