Analisis Kehandalan Proteksi Rele Arus Lebih Pada Jaringan Distribusi 20 kV Gardu Induk Singkil Tommy Wiranata Putra Pamungkas; Solly Aryza; Zuraidah Tharo
Jurnal Nasional Teknologi Komputer Vol 6 No 4 (2026): Oktober 2026
Publisher : CV. Hawari

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.61306/jnastek.v6i4.566

Abstract

The reliability of the protection system in a 20 kV distribution network is influenced by the accuracy of the Overcurrent Relay (OCR) and Ground Fault Relay (GFR) settings in detecting and isolating faults. This study aims to analyze the reliability of the overcurrent protection system in the 20 kV distribution network at Singkil Substation, focusing on feeders RI-02 and RI-04. A quantitative descriptive method was employed through system modeling and short-circuit current simulation using ETAP software. The data included 150 kV source parameters, a 30 MVA 150/20 kV power transformer, conductor data, OCR and GFR settings, recloser data, and fault currents at the feeder origin, recloser location, and feeder end. The analysis results indicate that the OCR setting of 380 A remains safe against the maximum load currents of 80 A for RI-02 and 100 A for RI-04. The RI-02 OCR remains sensitive to three-phase and two-phase faults up to the end of the feeder. However, the RI-04 OCR is not sensitive to two-phase faults at the feeder end because the fault current of 337 A is lower than the OCR setting. The GFR setting of 240 A is not sensitive to single-phase-to-ground faults at the end of RI-02 and RI-04, with fault currents of 212 A and 136 A, respectively. Therefore, the OCR and GFR settings need to be evaluated and adjusted by considering circuit breaker and recloser coordination to achieve a more selective, sensitive, and reliable protection system.