Aditiya Nathan Hidayat
Program Studi Teknik Mesin, Fakultas Teknik, Universitas Majalengka

Published : 1 Documents Claim Missing Document
Claim Missing Document
Check
Articles

Found 1 Documents
Search

PERAWATAN SOOTBLOWER INSERTABLE ROTATING (IR) PADA BOILER UNIT 3 PT PLN NUSANTARA POWER UP PLTU INDRAMAYU Aditiya Nathan Hidayat; Engkos Koswara
SEMINAR TEKNOLOGI MAJALENGKA (STIMA) Vol 10 (2026)
Publisher : Universitas Majalengka

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

This study discusses the maintenance of an Insertable Rotating (IR-3Z) sootblower on Boiler Unit 3 at PT PLN Nusantara Power UP PLTU Indramayu. Ash and soot deposits on boiler heat-transfer surfaces can create slagging and fouling, reduce heat absorption, and disturb boiler performance. The study aimed to describe the IR-3Z maintenance sequence, identify the main problems found during field practice, and determine the actions required to restore equipment performance. Data were obtained through field observation, interviews with company personnel, literature review, technical data collection, and direct participation in maintenance activities. The results show that routine maintenance includes mechanical inspection, drive-system evaluation, cleaning, lubrication, component replacement, and post-maintenance testing. The main actions observed were replacement of the guide-bar retaining screw, grease filling on the main drive gear, replacement of gland packing, and replacement of the gooseneck. Based on the technical parameters, the lance travels 267 mm at 290 mm/min, requiring approximately 0.92 min for one movement, while the 2.3 rpm rotation speed produces about two rotations during the operating stroke. The work-practice findings report that 75% of the identified problems were related to component wear and 25% to drive-mechanism disturbances. Scheduled maintenance and compliance with safety procedures are required to maintain sootblower reliability and boiler heat-transfer performance.