Analisis Kerusakan Kompresor HVAC untuk Tindakan Perawatan di PT. Supreme Energy Muara Labuh Egi Candra Adrial; Risal Abu; Mukhnizar Mukhnizar
Jurnal Teknik Industri Terintegrasi (JUTIN) Vol. 9 No. 4 (2026): October
Publisher : LPPM Universitas Pahlawan Tuanku Tambusai

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31004/jutin.v9i4.64721

Abstract

An HVAC system serves not only to regulate room temperature but also to maintain air quality, humidity, and the overall comfort and safety of the work environment. The reliability of an HVAC system depends on the performance of its key components. However, inadequate maintenance can lead to minor issues that may eventually escalate into serious problems. This study aims to analyze the failures that occur, evaluate the current maintenance system, and propose an improved maintenance approach. Based on an analysis using the Failure Mode and Effects Analysis (FMEA) method, five potential failures in an HVAC compressor were identified: low suction pressure, high discharge pressure, refrigerant leakage, expansion valve failure, and compressor overheating. The calculated Risk Priority Number (RPN) values ​​are as follows: high discharge pressure (216), compressor overheating (200), low suction pressure (192), refrigerant leakage (160), and expansion valve failure (140).